Ukukhetha izixhobo zekhebula lombane ezingaphantsi kwe-35kV

Ungayazi yonke imveliso emitsha epapashwa apha, kwaye ubone ukukhula kwethu kunye nokuvelisa izinto ezintsha.

Ukukhetha izixhobo zekhebula lombane ezingaphantsi kwe-35kV

Umhla: 09-17-2021

1. Isigama
1.1 Umgca wentambo
Yonke le nkqubo yenziwe ngeentambo, izixhobo, izixhobo ezincedisayo kunye nezixhobo ezincedisayo.
1.2 Izixhobo zekhebula
Iiterminal zekhebula, iijoyinti kunye neebhokisi zoxinzelelo lwekhebula ezizaliswe yioyile zibizwa ngokuba zizixhobo zekhebula;

1.3 Izixhobo zokuncedisa ngentambo
Igama eliqokelelweyo lezinto zesekethe yekhebula ezifana nebhokisi yokudibanisa enqamlezileyo, ibhokisi yokumisa umhlaba, umkhuseli womaleko okhuselayo, kunye nenkqubo yokubeka esweni;
1.4 Izixhobo ezincedisayo zekhebula
Igama eliqhelekileyo lezinto ezisetyenziswa kwiintambo zekhebula ezifana neentambo zekhebula, iibrakethi, iibhulorho kunye nezakhiwo.
Umaleko wezixhobo ze-1.5
Ingubo eyenziwe ngeteyiphu yesinyithi okanye ucingo. Ihlala isetyenziselwa ukukhusela intambo kwimikhosi yangaphandle yoomatshini.
1.6 Ukupheliswa kwentambo
Ikwaziwa njengentloko yekhebula, sisixhobo esifakwe ekupheleni kwekhebula ukuze sidibanise ikhebula nezinye izixhobo zombane okanye imigca yokudlulisa ephezu kwentloko kwaye sigcine ubushushu bufikelele kwindawo yokudibanisa.

1.7Isixhumi sentambo
Isixhobo esidibanisa umqhubi, ubushushu, umaleko wokukhusela kunye nomaleko wokukhusela wentambo kwintambo ukuze umgca wentambo uqhubeke.
1.8 Ikhaka lesinyithi
Yenziwe ngebhanti enye okanye ezingaphezulu zesinyithi, ii-braids zesinyithi, iileya ezixineneyo zeengcingo zesinyithi, okanye ulwakhiwo oludibeneyo lweengcingo zesinyithi kunye neebhanti zesinyithi.
2. Ukukhetha izixhobo zekhebula
2.1 Ukwakheka kwentloko yentambo
Ngokwembono yeentambo ezingundoqo ezintathu, izixhobo zentambo ziquka ikakhulu iintloko ezintathu zesiphelo ezincibilikayo ezibandayo, isingxobo esinye seminwe emithathu esincibilikayo esibandayo, iisheath ezintathu ezincibilikayo ezibandayo (okanye iityhubhu zokukhusela ezincibilikayo ezibandayo), iityhubhu ezintathu zokuvala ezincibilikayo ezibandayo, kunye nocingo oluphantsi olunye.

 

2.2 Uhlu lweentloko zekhebula
Ngokwevolthi yokusebenza, yahlulwe yaba: 1kV, intloko yentambo ye-10kV, intloko yentambo ye-35kV;
Ngokwemiqathango yokusetyenziswa, yahlulwe yaba: iiterminal zangaphandle, iiterminal zangaphakathi, kunye nezihlanganisi eziphakathi;
Ngokwenani lee-cores zekhebula, yahlulwe yaba: i-terminal ene-core enye, i-terminal ene-core ezintathu, i-terminal ene-core ezine, kunye ne-terminal ene-core ezintlanu.
Ngokwezixhobo zokufakela, yahlulwe yaba: intloko yesiphelo sentambo encibilikayo eshushu kunye nentloko yesiphelo sentambo encibilikayo ebandayo;

2.3.2 Ububanzi obusebenzayo becandelo elinqamlezileyo lentambo

Igama lemveliso

Inombolo yemveliso

Icandelo elisebenzayo lentambo (mm²)

Isiphelo sangaphakathi esine-core ezine esincinci se-1kV

I-NLS-1/4.0

10~16

I-NLS-1/4.1

25~50

I-NLS-1/4.2

70~120

I-NLS-1/4.3

150~240

I-NLS-1/4.4

300~400

I-10kV ebandayo enokushwabana enezikhombisi ezintathu eziphakathi

I-JLS-10/3.1

25~50

I-JLS-10/3.2

70~120

I-JLS-10/3.3

150~240

I-JLS-10/3.4

300~400

Isiphelo sangaphandle se-35kV esingundoqo esinye

I-WLS-35/1.1

50~95

I-WLS-35/1.2

120~240

I-WLS-35/1.3

300~400

I-WLS-35/1.4

500~800

Qaphela 1: Umbhobho wokukhusela wentloko yesiphelo ngokubanzi ubude bawo buyi-650mm, kodwa ungandiswa ube yi-800mm, 1000mm, 1200mm ngokweemfuno zabathengi.

Inqaku lesi-2: Intloko yesiphelo sentambo ye-XLPE isebenzisa ubuchwepheshe beengcingo eziphindwe kabini, oko kukuthi ingcingo yomhlaba ekhuselweyo kunye nengcingo yomhlaba ekhuselweyo yobhedu.

Qaphela 3: Xa uxela ngezinto ezincedisayo ze-intermediate joint, qaphela ingxelo exhasayo: i-cable waterproof kunye nebhokisi engaqhumiyo

2.3.3 Isixhumi seplagi yekhebula 1) Sisetyenziswa kakhulu ekuqhagamshelweni kwee-transformer zebhokisi, iibhokisi zenethiwekhi yeringi, iibhokisi zesebe, ii-transformer ezingcwatywe kunye nezinye izixhobo. Sisiphelo seplagi esigqunywe ngokupheleleyo kwaye sivalwe ngokupheleleyo.

2) Uhlulo:
A. Yahlulwe yaba ziintloko zeplagi ze-10kV, intloko yeplagi ye-20kV, intloko yeplagi ye-35kV ngokwenqanaba levolthi; B. Yahlulwe yaba ziintloko zeplagi zaseYurophu kunye neentloko zeplagi zaseMelika. Iintloko zeplagi zesitayile saseYurophu zahlulwe zaba: Isixhumi esingaphambili sesitayile saseYurophu, isixhumi esingasemva sesitayile saseYurophu, kunye nesithinteli sombane esiqhagamshelwe ngasemva; zisetyenziswa kakhulu ekuqhagamshelweni kweebhokisi zenethiwekhi yeringi, iitransformer zebhokisi zesitayile saseYurophu, kunye nezixhobo zebhokisi yesebe yesitayile saseYurophu. Ziintloko zesiphelo seplagi ezigqunyiweyo ngokupheleleyo kwaye zivaliwe ngokupheleleyo. Intambo kunye nezixhobo ziqhagamshelwe ngentambo yokudibanisa yohlobo lwebholiti. Iintloko zeplagi zaseMelika zahlulwe zaba zii: 200A American elbow head, 600A American III-generation T-shaped head. Isetyenziswa kakhulu ekuqhagamshelweni kweebhokisi zenethi zeringi zaseMelika, iitransformer zebhokisi zaseMelika, kunye neebhokisi zesebe zaseMelika. Sisiphelo seplagi esigqunyiweyo ngokupheleleyo kwaye sivaliwe ngokupheleleyo. Uqhagamshelo lweplagi luyasetyenziswa phakathi kwentambo kunye nesixhobo.
Okwesithathu, ukhetho lommandla womaleko wokukhusela isinyithi wentambo ye-polyethylene edityanisiweyo
3.1 Ukusila ikhaka lesinyithi
NgokweNqaku 4.1.10~4.1.11 le-GB 50217-2018 Power Engineering Cable Design Standard: 4.1.10 Umkhono wesinyithi wentambo yamandla kufuneka usekelwe ngqo. I-metal sheath yentambo ye-3-core kwinkqubo ye-AC kufuneka isekelwe ngqo kwi-terminals ezimbini kunye neendawo zokudibanisa umgca wentambo.
4.1.11 Isiciko sesinyithi sentambo yamandla ye-AC enye-core kufuneka sisekelwe ngqo ubuncinane kwelinye icala, kwaye ixabiso eliphezulu le-normal induced potential kuyo nayiphi na isiphelo esingasekelwe ngqo kufuneka lihlangabezane neemfuno ezilandelayo:
1. Xa amanyathelo okhuseleko anokuthintela ngempumelelo abasebenzi ekunxibelelaneni ngokungekho mthethweni nesingxobo sesinyithi engathathwanga, i-voltage ayizukudlula i-50V;
2. Ngaphandle kweemeko ezichazwe kumhlathi 1 wale nqaku, akufuneki idlule kwi-300V;
3. Amandla aqhelekileyo abangelwa yi-metal sheath yentambo enye ye-AC system kufuneka abalwe ngokwefomula ekwiSihlomelo F salo mgangatho.
4.1.13 Ukuba ishelufu yesinyithi yeentambo zombane ezine-single-core ezingaphantsi kwe-35kV isekelwe ngqo kwindawo enye, kwaye kukho imfuneko yokukhusela ishelufu eqinisiweyo, umda we-voltage yeshelufu unokufakelwa kwisiphelo esingagungqiyo somgca.

3.2 Ukukhethwa kwendawo enqamlezileyo yomaleko wokukhusela isinyithi
Ngokwe-Article 6.3.1 ye-DL/T401-2002 High-Voltage Cable Selection Guidelines: Kwi-extruded insulated metal shielding shield layer without metal sleeve, xa i-conductor cross-section ingama-240mm² nangaphantsi, i-copper tape ingasetyenziselwa ukuzikhusela, kodwa xa i-conductor cross-section inkulu kune-240mm² kufuneka ikhuselwe ngocingo lobhedu. I-cross-section ye-metal shield kufuneka ihlangabezane neemfuno zexesha elifutshane xa kwenzeka i-single-phase ground fault okanye ii-two-time faults kwiindawo ezahlukeneyo.